Cable voltage drop and size

Enter the current, route length and cable size to see the drop in volts and percent. The second mode picks the smallest standard size.

Voltage drop
V
A
m
°C

Result

Voltage drop6.857V
Relative drop2.98%
Voltage at the load
223.1 V
Power lost in the cable
109.7 W
Conductivity γ
56 m/(Ω·mm²)

ΔU = 2 · L · I · cos φ / (γ · S)

Voltage drop for standard sizes
SizeΔUΔU %Loss
1.5 mm²11.4 V4.97%183 W
2.5 mm² ←6.86 V2.98%110 W
4 mm²4.29 V1.86%68.6 W
6 mm²2.86 V1.24%45.7 W
10 mm²1.71 V0.745%27.4 W
16 mm²1.07 V0.466%17.1 W
25 mm²0.686 V0.298%11 W
35 mm²0.49 V0.213%7.84 W
50 mm²0.343 V0.149%5.49 W
70 mm²0.245 V0.106%3.92 W
95 mm²0.18 V0.0785%2.89 W
120 mm²0.143 V0.0621%2.29 W
150 mm²0.114 V0.0497%1.83 W
185 mm²0.0927 V0.0403%1.48 W
240 mm²0.0714 V0.0311%1.14 W

This method only uses conductor resistance, not reactance, so it underestimates the drop above roughly 50 mm². It doesn’t check current-carrying capacity or protection: confirm the cable choice against IEC 60364.

Embed on your site

Paste this code into your page’s HTML. The tool sets its own height, and the link to Kalkio has to stay visible.

Calculator by Kalkio · kalkio.app

How voltage drop is calculated

Current through a cable causes a drop across its resistance. In a single-phase circuit the current goes out and back, hence the factor 2: ΔU = 2 · L · I · cos φ / (γ · S). In a balanced three-phase system the factor is √3 and the result refers to the line-to-line voltage.

γ is conductivity: 56 m/(Ω·mm²) for copper and 34 for aluminium at 20 °C. At operating temperature (up to 70 °C for PVC insulation) resistance rises by about 20%, and the drop with it.

What drop is allowed?

IEC 60364-5-52 recommends that the drop from the origin of the installation to the load stays within 3% for lighting and 5% for other uses when supplied from the public network. Many designers use 3% for final circuits.

Common questions

Which length do I enter?

The one-way route length from the board to the load. The factor in the formula already accounts for the return conductor.

Is this enough to size a cable?

No. The cable must also carry the current for its installation method, coordinate with the protective device and ensure automatic disconnection.